Common Area Violations

Building ID 820815 · 20 violations
Violation 19224951 Other Class B
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AT DOOR AT EAST WALL LEADING TO FIRE STAIR AT PUBLIC HALL, 1st STORY
Apartment: —   |   Story: 1
Inspection: 2026-09-17T00:00:00.000
Status: NOV SENT OUT
Violation Corrected (NYC): No
Violation 19224950 Other Class C
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH SET AT PUBLIC HALL STAIRS AT EAST , 1st STORY
Apartment: —   |   Story: 1
Inspection: 2026-09-17T00:00:00.000
Status: NOV SENT OUT
Violation Corrected (NYC): No
Violation 19202434 Other Class C
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT DOOR AT COMPACTOR CLOSET, 5th STORY
Apartment: —   |   Story: 5
Inspection: 2026-09-08T00:00:00.000
Status: NOV SENT OUT
Violation Corrected (NYC): No
Violation 19163601 Other Class C
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT HOOPER CHUTE DOOR AT COMPACTOR CLOSET AT PUBLIC HALL, 8th STORY
Apartment: —   |   Story: 8
Inspection: 2026-08-25T00:00:00.000
Status: NOV SENT OUT
Violation Corrected (NYC): No
Violation 19163602 Other Class C
HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES AT COMPACTOR CLOSET, 2nd STORY
Apartment: —   |   Story: 2
Inspection: 2026-08-25T00:00:00.000
Status: NOV SENT OUT
Violation Corrected (NYC): No
Violation 19145264 Other Class C
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH SET AT NORTH STAIRCASE DOOR AT PUBLIC HALL, 1st STORY
Apartment: —   |   Story: 1
Inspection: 2026-08-15T00:00:00.000
Status: NOV SENT OUT
Violation Corrected (NYC): No
Violation 19145242 Other Class A
§ 26-1103 ADMIN. CODE: POST AND MAINTAIN A PROPER NOTICE ON WALL OF THE ENTRANCE STORY IN ENGLISH AND SPANISH ON THE AVAILABILITY OF THE AGENCYS HOUSING INFORMATION GUIDE. A SAMPLE NOTICE CAN BE FOUND AT WWW.NYC.GOV/HPD. AT PUBLIC HALL, 1st STORY
Apartment: —   |   Story: 1
Inspection: 2026-08-15T00:00:00.000
Status: NOV SENT OUT
Violation Corrected (NYC): No
Violation 19145270 Other Class B
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AND ITS ASSEMBLY AT NORTH STAIRCASE DOOR AT PUBLIC HALL, 1st STORY
Apartment: —   |   Story: 1
Inspection: 2026-08-15T00:00:00.000
Status: NOV SENT OUT
Violation Corrected (NYC): No
Violation 19123994 Other Class B
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCHSET AT STAIRCASE 2 AT PUBLIC HALL, 4th STORY
Apartment: —   |   Story: 4
Inspection: 2026-08-04T00:00:00.000
Status: NOV SENT OUT
Violation Corrected (NYC): No
Violation 19112165 Other Class B
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH AND ITS ASSEMBLIES AT DOOR TO STAIRCASE 1 AT PUBLIC HALL STAIRS
Apartment: —   |   Story: 0
Inspection: 2026-07-27T00:00:00.000
Status: NOV SENT OUT
Violation Corrected (NYC): No
Violation 19098863 Other Class B
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH AND ITS ASSSMEBLIES AT BULKHEAD DOOR AT 2nd PUBLIC HALL BULKHEAD FROM NORTH, 8th STORY
Apartment: —   |   Story: 8
Inspection: 2026-07-22T00:00:00.000
Status: NOV SENT OUT
Violation Corrected (NYC): No
Violation 19098860 Other Class B
§ 27-2005 ADM CODE PROVIDE UNLOCKABLE SLIDE BOLT OR HOOK INSTALLED ON DOOR THAT ALLOWS RE-ENTRY FROM ROOF TO PUBLIC HALL AT 2nd PUBLIC HALL BULKHEAD FROM NORTH, 8th STORY
Apartment: —   |   Story: 8
Inspection: 2026-07-22T00:00:00.000
Status: NOV SENT OUT
Violation Corrected (NYC): No
Violation 19098864 Other Class C
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGE AT HOPPER CHUTE DOOR AT COMPACTOR CLOSET, 8th STORY
Apartment: —   |   Story: 8
Inspection: 2026-07-22T00:00:00.000
Status: NOT COMPLIED WITH
Violation Corrected (NYC): Yes  |  Date of Correction: 2026-08-11T00:00:00.000
Violation 19060663 Other Class B
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE SPRING BALANCE LOWER WINDOW SASH AT WINDOW IN FRONT OF APT 4U AT PUBLIC HALL, 4th STORY
Apartment: —   |   Story: 4
Inspection: 2026-07-09T00:00:00.000
Status: NOV CERTIFIED ON TIME
Violation Corrected (NYC): Yes  |  Date of Correction: 2026-08-31T00:00:00.000
Violation 19060662 Other Class A
§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CEILING PUBLIC HALL AT PUBLIC HALL, 1st STORY
Apartment: —   |   Story: 1
Inspection: 2026-07-09T00:00:00.000
Status: NOV SENT OUT
Violation Corrected (NYC): No
Violation 19060661 Other Class B
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT PUBLIC HALL, 1st STORY
Apartment: —   |   Story: 1
Inspection: 2026-07-09T00:00:00.000
Status: NOV CERTIFIED ON TIME
Violation Corrected (NYC): Yes  |  Date of Correction: 2026-08-31T00:00:00.000
Violation 19042524 Other Class C
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES TO HOPPER DOOR AT REFUSED ROOM AT PUBLIC HALL, 1st STORY
Apartment: —   |   Story: 1
Inspection: 2026-06-29T00:00:00.000
Status: NOT COMPLIED WITH
Violation Corrected (NYC): Yes  |  Date of Correction: 2026-07-14T00:00:00.000
Violation 19029923 Other Class A
§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL, 1st STORY
Apartment: —   |   Story: 1
Inspection: 2026-06-25T00:00:00.000
Status: NOV SENT OUT
Violation Corrected (NYC): No
Violation 18994331 Other Class A
§27-2045(B)(5) HMC, § 12-01 RCNY POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAILBOX SIGNAGE PRESENT BUT INFORMATION MISSING AT PUBLIC HALL, 1st STORY
Apartment: —   |   Story: 1
Inspection: 2026-06-10T00:00:00.000
Status: NOV SENT OUT
Violation Corrected (NYC): No
Violation 18994330 Other Class A
§27-2045(B)(5) HMC, § 12-06, 12-10 RCNY POST A PROPER NOTICE OF CARBON MONOXIDE DETECTING DEVICE REQUIREMENTS, IN A FORM APPROVED BY COMMISSIONER, IN A COMMON AREA OF A CLASS A MULTIPLE DWELLING NEAR INSPECTION CERTIFICATE OR PROVIDE NOTICE TO TENANTS IN PRIVATE DWELLINGS SIGNAGE PRESENT BUT INFORMATION MISSING
Apartment: —   |   Story: 1
Inspection: 2026-06-10T00:00:00.000
Status: NOV SENT OUT
Violation Corrected (NYC): No